Made Easy Tool for DEFINITY Media Server Configurations
Issue 4, May 2002
Install and Connect MCC1 (Multicarrier) Cabinet
Check Commercial Power and Connect AC Power
Before powering up the system, check the AC power using a KS-20599 digital voltmeter (DVM) (or equivalent).
- Set the DVM to the 250 volt range.
- Carefully measure the voltage between the hot and neutral side of the receptacle. The neutral wire is white, the hot wire is black.
- Verify the meter reads 106 to 128 VAC. If not, have a qualified electrician correct the problem.
- Measure the voltage between the neutral and ground side of the receptacle. The ground wire is green.
- Verify the meter reads 0 VAC. If not, have a qualified electrician correct the problem.
- Set all cabinet power modules OFF. Plug the AC power cable into the receptacle.