WARNING: The following recommended test equipment, tests and diagrams are intended only for North American installations at 110 to 125 Volts AC. For installations in other regions, have a licensed electrician verify the ground and voltages.
WARNING: If the AC outlet tests indicate that the power requirements are not met, your customer must contact a licensed electrician. DO NOT install the system until all requirements are met.
If the AC outlet tests that follow reveal any of the following conditions, they must be corrected BEFORE the system is to be installed.
WARNING: Hazardous voltages are present during this test. Follow all instructions carefully when working the AC power line voltages.
Verify Ground Using an Ideal 61-035 Circuit Tester (or equivalent)
Begin _____________________
If the circuit is properly grounded, the yellow and white lights on the tester illuminate
WARNING: If the tester indicates any type of ground fault, your customer must contact a licensed electrician. DO NOT install the system.
Verify Voltages Using a Volt-Ohm Millimeter (VOM) (U.S. and countries using 110 to 125 V AC power)
Begin _____________________
WARNING: Hazardous voltages are present during this test. Follow all instructions carefully when working with AC power line voltages.
|
1. Phase to neutral should be 110 to 125 V AC. |
If the voltage readings do not measure the values given, the AC outlet is improperly wired. DO NOT INSTALL THE SYSTEM. Advise the customer to have a licensed electrician correct the problem.
You are ready to power the system.
|
|
|