Install Coupled Bonding Conductor ���
The Coupled Bonding Conductor (CBC) provides mutual inductance coupling between the CBC and the telephone cables exposed to lightning. The conductor can be a 10 AWG (#25) (6�square millimeters) wire tie wrapped to the exposed cables, a metal cable shield around the exposed cables, or 6 spare pairs from the exposed cable.
For a high-rise building, connect the CBC to an approved building ground on each floor. To provide the coupled bonding protection:
- Connect one end of the conductor to a telephone cable building entrance protector ground that is connected to an approved ground.
- Route the conductor next to the exposed telephone cables being protected until it reaches the crossconnect nearest to the telephone system.
- Position the nonexposed telephone cables at least 12 inches (30.5 centimeters) away from exposed telephone cables whenever possible.
- Terminate the other end to the single-point ground block provided for the telephone system.