DEFINITY Made Easy Tools
Issue 3, December 2001
Install and Wire Telephone Power Supply
1151A1 and 1151A2 Power Supplies
The 1151A1 and 1151A2 Power Supplies comply with the UL Standard UL 1950, second edition.
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
DEFINITY Made Easy Tools
Issue 3, December 2001
Install and Wire Telephone Power Supply
The 1151A1 and 1151A2 Power Supplies comply with the UL Standard UL 1950, second edition.
For safety instructions, see Important Safety Instructions for 1151A1 and 1151A2 Power Supplies. For installation instructions, see Connect the 1151A1 or 1151A2 Power Supplies.
The 1151A1 and 1151A2 Power Supplies can be used to supply local power to ISDN-T 65xx, 74xx, 75xx, 84xx, and 85xx series voice terminals connected to a system and to the 302C1 Attendant Console that requires auxiliary power for its display. The unit can supply power to adjunct equipment such as S201A and CS201A speakerphones or a 500A Headset Adapter attached to any currently manufactured analog, DCP, or ISDN-T voice terminal equipped with an adjunct jack.
Caution! | The power supply can be used only with telecommunications equipment, indoors, and in a controlled environment. |
The power supply has a single output of -48 VDC, 0.4 Amps, and can operate from either a 120 VAC 60 Hz power source (105 to 129 VAC) or a 220/230/240 VAC 50 Hz power source (198 to 264 VAC). Input voltage selection is automatic. The output capacity is 19.2 Watts.
The power supply can be placed on a flat surface such as a desk. For wall-mounting, keyhole slots are provided on the bottom of the chassis.
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
Copyright� 2001 Avaya Inc. |
Send comments to MadeEasy Development Team |
Always check at the Made Easy Web site for the most current information. |