Install and Connect MCC1 (Multicarrier) Cabinet
Connect Small Battery Holdover
Connect the small battery holdover cable to J20. See Power Distribution Unit (J58890CH).
Power Distribution Unit (J58890CH)
Figure Notes:
- Connect small battery holdover cable (or temperature sensor cable from large battery cabinet) to J20
- Carrier Circuit Breakers
- Ground Terminal Block
- Connect -48 VDC Return - 1 AWG (50 mm 2) red cable here.
- Connect -48 VDC - 1 AWG (50 mm 2) black cable
- 1 AWG (50 mm 2) 50 ft (15.2 m) cable to large battery cabinet. For cables greater than 50 ft (15.2 m), contact your Avaya representative.
- Ground Terminal Block
- To AC load center or approved single-point ground block
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |