Made Easy Tool for DEFINITY Media Server Configurations
Issue 5, October 2002
Install and Connect MCC1 (Multicarrier) Cabinet
Connect Large Battery Holdover
When using large battery holdover, 1 battery cabinet is required for every system cabinet requiring holdover. The 24-cell battery cabinet must have a float voltage of 54.2 VDC.
- Connect the -48 VDC cable to the large battery connector. See Power Distribution Unit (J58890CH).
- Connect the -48 VDC RETURN cable to the ground terminal block.
- Connect the temperature sensor cable, from the battery cabinet, to J20.