S8300 Alarms--UPS

See Table 27 through Table 43 for a list of S8300 Alarms--UPS.

Table 27. Alarm #49
Number
49
Source
UPS
Event ID
1-8
Alarm Level
Major (SUP)
Alarm Text Description
upsEstimatedMinutesRemaining
Possible Causes
UPS does not have AC power source
Determining Cause
Alarm condition present indicates the problem occurred.
Resolution
Return AC power to UPS

Table 28. Alarm #50
Number
50
Source
UPS
Event ID
12
Alarm Level
Major
Alarm Text Description
upsAlarmShutdownPending
Possible Causes
A shutdown-after-delay countdown is underway -- i.e., the UPS has been commanded off
Determining Cause
Alarm condition present indicates the problem occurred.
Resolution

Table 29. Alarm #51
Number
51
Source
UPS
Event ID
13
Alarm Level
Major
Alarm Text Description
upsAlarmShutdownImminent
Possible Causes
UPS will turn off power to the load in less than 5 seconds
Determining Cause
Alarm condition present indicates the problem occurred.
Resolution
Return AC power to UPS

Table 30. Alarm #52
Number
52
Source
UPS
Event ID
14
Alarm Level
Major
Alarm Text Description
upsAlarmDepletedBattery
Possible Causes
The UPS will be unable to sustain the present load when and if the utility power is lost
Determining Cause
Alarm condition present indicates the problem occurred.
Resolution
Batteries need to be charged or replaced

Table 31. Alarm #53
Number
53
Source
UPS
Event ID
15
Alarm Level
Major
Alarm Text Description
upsAlarmBatteryBad
Possible Causes
One or more batteries needs to be replaced
Determining Cause
Alarm condition present indicates the problem occurred.
Resolution
Replace battery(ies)

Table 32. Alarm #54
Number
54
Source
UPS
Event ID
16
Alarm Level
Minor
Alarm Text Description
upsAlarmInputBad
Possible Causes
An input condition is out of tolerance
Determining Cause
Alarm condition present indicates the problem occurred.
Resolution
provide appropriate AC power to the UPS

Table 33. Alarm #55
Number
55
Source
UPS
Event ID
17
Alarm Level
Minor
Alarm Text Description
upsAlarmTempBad
Possible Causes
A temperature is out of tolerance.
Determining Cause
Alarm condition present indicates the problem occurred.
Resolution
Change environment temperature (increase or decrease depending on which has occurred) or change alarming thresholds

Table 34. Alarm #56
Number
56
Source
UPS
Event ID
18
Alarm Level
Minor
Alarm Text Description
upsAlarmCommunicationsLost
Possible Causes
A problem has been encountered in the communications between the agent and the UPS.
Determining Cause
Alarm condition present indicates the problem occurred.
Resolution
requires diagnosing the UPS -- may be simpler to just replace it and diagnose it later

Table 35. Alarm #57
Number
57
Source
UPS
Event ID
19
Alarm Level
Warning
Alarm Text Description
upsAlarmBypassBad
Possible Causes
bypass is out of tolerance
Determining Cause
Alarm condition present indicates the problem occurred.
Resolution
return AC input power to UPS

Table 36. Alarm #58
Number
58
Source
UPS
Event ID
20
Alarm Level
Warning
Alarm Text Description
upsAlarmLowBattery
Possible Causes
remaining battery run-time is less than or equal to specified threshold
Determining Cause
Alarm condition present indicates the problem occurred.
Resolution
return AC input power to UPS

Table 37. Alarm #59
Number
59
Source
UPS
Event ID
21
Alarm Level
Warning
Alarm Text Description
upsAlarmUpsOutputOff
Possible Causes
UPS has shutdown output power as requested
Determining Cause
Alarm condition present indicates the problem occurred.
Resolution
turn-on output power -- can be done via SNMP messages

Table 38. Alarm #60
Number
60
Source
UPS
Event ID
22
Alarm Level
Warning
Alarm Text Description
upsAlarmOutputBad
Possible Causes
output on one of the receptacles is out of tolerance
Determining Cause
Alarm condition present indicates the problem occurred.
Resolution
requires diagnosing the UPS -- may be simpler to just replace it and diagnose it later

Table 39. Alarm #61
Number
61
Source
UPS
Event ID
23
Alarm Level
Warning
Alarm Text Description
upsAlarmOutputOverload
Possible Causes
load on the UPS exceeds its output capacity
Determining Cause
Alarm condition present indicates the problem occurred.
Resolution
reduce the load on the UPS

Table 40. Alarm #62
Number
62
Source
UPS
Event ID
24
Alarm Level
Warning
Alarm Text Description
upsAlarmChargerFailed
Possible Causes
UPS charger has failed
Determining Cause
Alarm condition present indicates the problem occurred.
Resolution
requires diagnosing the UPS -- may be simpler to just replace it and diagnose it later

Table 41. Alarm #63
Number
63
Source
UPS
Event ID
25
Alarm Level
Warning
Alarm Text Description
upsAlarmFanFailure
Possible Causes
one or more UPS fans have failed
Determining Cause
Alarm condition present indicates the problem occurred.
Resolution
fix fan

Table 42. Alarm #64
Number
64
Source
UPS
Event ID
26
Alarm Level
Warning
Alarm Text Description
upsAlarmFuseFailure
Possible Causes
one or more UPS fuses have failed
Determining Cause
Alarm condition present indicates the problem occurred.
Resolution
replace fuse

Table 43. Alarm #65
Number
65
Source
UPS
Event ID
27
Alarm Level
Warning
Alarm Text Description
upsAlarmGeneralFault
Possible Causes
general fault in the UPS has occurred
Determining Cause
Alarm condition present indicates the problem occurred.
Resolution
requires diagnosing the UPS -- may be simpler to just replace it and diagnose it later