Connect Small Battery Holdover

Return to Task List

Connect the small battery holdover cable to J20. See Power Distribution Unit (J58890CH).

Power Distribution Unit (J58890CH)

Figure Notes:
      1. Connect small battery holdover cable (or temperature sensor cable from large battery cabinet) to J20

      2. Carrier Circuit Breakers

      3. Ground Terminal Block

      4. Connect -48 VDC Return - 1 AWG (50 mm 2) red cable here.

      5. Connect -48 VDC - 1 AWG (50 mm 2) black cable

      6. 1 AWG (50 mm 2) 50 ft (15.2 m) cable to large battery cabinet. For cables greater than 50 ft (15.2 m), contact your Avaya representative.

      7. Ground Terminal Block

      8. To AC load center or approved single-point ground block

Return to Task List