DEFINITY Made Easy Home Page Table of contents Previous page Next page Index Links Frequently asked questions
Go to Upgrades for si Go to Installation for MCC Go to Installation for SCC



Connect DC Power Cabinet Approved Ground

Return to Task List


Note: The wire must be at least as large as the largest distribution wire in the system (required by UL). In this example 1 AWG is used.

  1. At the DC Power Cabinet, connect a 1 AWG (#70) (44 mm 2) ground wire to the Ground Discharge Bar. See Typical Power and Ground for a DC-Powered Cabinet.

  2. Route the ground wire out of the cabinet and terminate it on the approved ground. The approved ground must be identified with a grounding tag (FORM 15657NR or equivalent). See Approved Grounds.

Return to Task List


DEFINITY Made Easy Home Page Table of contents Previous page Next page Index Links Frequently asked questions
Go to Upgrades for si Go to Installation for MCC Go to Installation for SCC
Copyright 2001 Avaya Inc.
Send comments to MadeEasy Development Team



Always check at the Made Easy Web site for the most current information.