Connect Ground Wires for DC-Powered Systems

Return to Task List


Caution! Do not connect any ground wires from an EPN cabinet to another EPN cabinet or to a PPN cabinet. All ground wires must be terminated at the single-point ground block at the main AC supply (AC mains).

  1. Connect a 6 AWG (#40) (16 mm 2) wire to the PPN cabinet ground terminal block.

  2. Route the wire to the AC mains single-point ground block and connect.

  3. Connect a 6 AWG (#40) (16 mm 2) wire to each EPN's cabinet ground terminal block.

  4. Route the wire(s) to the AC mains single-point ground block and connect.

  5. Connect a 6 AWG (#40) wire to the DC battery cabinet and DC power cabinet.

  6. Route wires to the AC mains single point ground block and connect them.