Install and Position Stratum 3 Clock Cabinet
Return to Task List
Check the location of the AC power receptacle. The receptacle must be on a separately fused circuit that is not controlled by a wall switch. It must be located within 10 ft (3 m) of the cabinet and should be located outside the MDF area.
- Position the clock cabinet in the designated location.
- If earthquake protection is required, skip to Install Earthquake Protection for SCC or Install Earthquake Protection for MCC.
- If earthquake protection is not required, level the cabinets and adjust and lock the cabinet stabilizing bolts to keep the cabinet from moving.
Return to Task List