DEFINITY Made Easy Home Page Table of contents Previous page Next page Index Links Frequently asked questions
Go to Upgrades for si Go to Installation for MCC Go to Installation for SCC



Connect DC Power Distribution Unit Ground

Return to Task List

  1. Measure and cut a length of 4 AWG (#5) (21 mm 2) wire long enough to reach between the GROUND DISCHARGE bar in the DC Power Cabinet and the GRD connector on the DC Distribution Unit. See DC Power Distribution Unit Ground.

  2. At the DC Power Cabinet, connect a the 4 AWG (#5) (21 mm 2) wire to the GROUND DISCHARGE bar.

  3. Route the opposite end of the wire to the DC Power Distribution Unit and connect the wire to the GRD connector.

  4. Repeat Steps 2 and 3 for each remaining DC Power Distribution Unit.

DC Power Distribution Unit Ground

Figure Notes:

Return to Task List


DEFINITY Made Easy Home Page Table of contents Previous page Next page Index Links Frequently asked questions
Go to Upgrades for si Go to Installation for MCC Go to Installation for SCC
Copyright 2002 Avaya Inc.
Send comments to MadeEasy Development Team



Always check at the Made Easy Web site for the most current information.