Replaced 655A Power Unit in slot 24A15. It solved the problem, and the alarm cleared:
status environment 24a
CABINET POWER SUPPLY STATUS (655A)
Pow Alm Temp(F/C) Hot Voltage FAN Ring Voltage Input
Loc Cnt InLet Exhst Spot +5 -5 -48 Ctrl Alm Stat Ctrl Set Det Power
24A00 0 91/33 87/31 ok 5.13 5.18 49.5 mid N ok actv 25HZ Y AC
24A15 0 89/32 86/30 ok 5.05 5.10 49.0 mid N ok stby 20HZ Y AC
Note: if replacement of 655A power supply does not resolve the error ---- the IPSI (TN2312BP) could be the issue.
The POW-SUP maintenance object notes the presence of each power supply and the voltage of each power supply in the G650.
This MO:
● Verifies that a power supply that is administered is physically present
● Verifies that each output voltage (+5V, -5V, and -48V for the power supplies and +12V for
the fan) is within tolerance
● Is used with the recycle carrier command to momentarily turn off and on the power to
a specified power supply or to a specified carrier
● Is used to turn off output voltages from one power supply to verify that the other supply can
support the entire load of the G650 (This is used only when a G650 has redundant power
supplies.)
655A Power Supply – cc700406135
TN2312BP IPSI – cc700260359