DEFINITY Made Easy Home Page Table of contents Previous page Next page Index Links Frequently asked questions
Go to Upgrades for si Go to Installation for MCC Go to Installation for SCC



Install Coupled Bonding Conductor Wires

Return to Task List

This is a conductor that connects to the single-point ground block and run adjacent to pairs in an associated cable. The mutual coupling between the CBC and the pairs reduces potential differences in terminating equipment. The conductor consists of a 10 AWG (#25) (6 mm 2) wire terminated at the CBC ground terminal bar at the Main Distribution Frame (MDF).

  1. At the DC Power Cabinet, connect a 10 AWG (#25) (6 mm 2) ground wire to the Ground Discharge Bar. See Typical Power and Ground for a DC-Powered Cabinet.

  2. Route the 10 AWG (#25) (6 mm 2) ground wire to the CBC ground terminal bar at the MDF. Be sure a minimum of 12 in. (30.5 cm) spacing is maintained between the CBC and other power and ground leads.

  3. Tie wrap the ground wire to the inside wiring cable.


Note: The ground wires are connected to the CBC as instructed in Install Telecommunications Cabling.

Return to Task List


DEFINITY Made Easy Home Page Table of contents Previous page Next page Index Links Frequently asked questions
Go to Upgrades for si Go to Installation for MCC Go to Installation for SCC
Copyright 2001 Avaya Inc.