DEFINITY Made Easy Home Page Table of contents Previous page Next page Index Links Frequently asked questions
Go to Upgrades for si Go to Installation for MCC Go to Installation for SCC



Connect DC Power to PPN and EPN Cabinets

Return to Task List

  1. Be sure the main circuit breaker is OFF.

  2. Measure and cut 2 pieces of 1 AWG (#70) (44 mm 2) wire long enough to reach from the DC Power Cabinet to the PPN cabinet.

  3. At the DC Power Cabinet, connect the -48 volt DC wire to the DC OUTPUT circuit breaker. See Typical Power and Ground for a DC-Powered Cabinet. Connect the -48 volt RTN (return) wire to the ground discharge bar.

  4. Route the wires out of the cabinet, through the hole in the lower rear cover, and to the PPN cabinet.

  5. Connect the -48 volt DC wire to the -48VDC terminal on the J58890CF Power Distribution Unit.

  6. Connect the -48 volt RTN wire to the -48RTN terminal on the J58890CF Power Distribution Unit terminal block.

  7. Repeat Steps 2 through 6 for each EPN and Auxiliary cabinet in the system.

Return to Task List


DEFINITY Made Easy Home Page Table of contents Previous page Next page Index Links Frequently asked questions
Go to Upgrades for si Go to Installation for MCC Go to Installation for SCC
Copyright 2001 Avaya Inc.
Send comments to MadeEasy Development Team



Always check at the Made Easy Web site for the most current information.