DEFINITY Made Easy Home Page Table of contents Previous page Next page Index Links Frequently asked questions
Go to Upgrades for si Go to Installation for MCC Go to Installation for SCC



Connect Stratum 3 Clock DC Power

Return to Task List

  1. Set the clock cabinet circuit breaker at the DC power plant OFF.

  2. At the clock cabinet, connect a 6 AWG (#40) (16 mm 2) ground wire to the -48V terminal on the terminal strip.

  3. At the clock cabinet, connect a 6 AWG (#40) (16 mm 2) wire to the -48VRTN terminal on the terminal strip.

  4. Route the wires out of the cabinet and to the DC power plant.

  5. At the DC power plant, connect the -48V wire to the DC OUTPUT circuit breaker.

  6. At the DC power plant, connect the -48VRTN wire to the DISCH GRD bar.

Return to Task List


DEFINITY Made Easy Home Page Table of contents Previous page Next page Index Links Frequently asked questions
Go to Upgrades for si Go to Installation for MCC Go to Installation for SCC
Copyright 2001 Avaya Inc.
Send comments to MadeEasy Development Team



Always check at the Made Easy Web site for the most current information.