Connect External Alarm Indicators and Auxiliary Power���

Alarms can be generated on adjunct equipment, sent to the media server, and recorded and reported as "external alarms." A typical major alarm input is from an Uninterruptible Power Supply (UPS).

The media server provides a relay contact that can operate a customer-provided alarm, such as a light or bell. The circuitry and power source are customer-provided. The alarm device must not exceed a rating of more than 100 volts at 0.75 amperes.

  1. Connect 1 major and 1 minor alarm input pair to the trunk/auxiliary field from the AUX connector. See Alarm Inputs at AUX Connector.
  2. Connect an external alarm output through pins 48 and 23 of the AUX connector. See Alarm Output at AUX Connector.
  3. Note which device connects to which alarm and give this information to your Avaya representative for troubleshooting purposes.
  4. Connect emergency transfer power and auxiliary power as shown in Emergency Transfer and Auxiliary Power. Auxiliary power includes power to an attendant console or adjunct device.

Alarm Inputs at AUX Connector
Color
AUX Connector
White-Blue
AP1 (Pin 26) Major Alarm Input
Blue-White
Ground (Pin 1)
White-Orange
AP2 (Pin 27) Minor Alarm Input
Orange-White
Ground (Pin 2)

Alarm Output at AUX Connector
Color
AUX Connector
Violet-Green
EXTALMA (Pin 48) Alarm Output
Green-Violet
EXTALMB (Pin 23) (Ground) Alarm Output

Emergency Transfer and Auxiliary Power
Color
AUX Connector
Black-Green
XFER48 (Emergency Transfer) (Pin 36)
Green-Black
Ground (Pin 11)
Black-Slate
ACC48A (Adjunct -48 VDC) (Pin 19)
Slate-Black
Ground (Pin 44)