Connect Power Distribution Unit External Alarm Wires���
The external alarm plug should already be connected to the J58890CH-1 Power Distribution Unit. The pinout for the connector is shown in External Alarm Connector Pinout.
NOTE: RS232 alarms (RXD, DTR, DSR, TXD, RS-232 GRD, and RTS) are not supported on the BU3200A Battery Interface Unit.
- Choose an alarm to connect (such as Battery Interface Failure).
- Choose the port circuit pack to use and its carrier and slot number (from Port Circuit Pack and Telephone Pin Designations). For example, TN2183 Analog Line, cabinet 1, carrier C, slot 1.
- Choose a port circuit on the port circuit pack, for example port 3.
- Install cross-connect jumpers to connect the named pins from the alarm wires to the appropriate pins on the port circuit pack.
NOTE: It is recommended that the RFA, ACF, and BIF alarm leads be connected to the major alarm device and the BOD alarm leads be connected to the minor alarm device.
- Connect the major and minor alarm devices to the appropriate cross-connect pins on the MDF.
- Administer the alarms using the Administrator's Guide for Avaya MultiVantage Software.
External Alarm Connector Pinout �
| Pin |
Designation |
Definition |
| 26 |
Not Used |
� |
| 1 |
Not Used |
� |
| 27 |
Not Used |
� |
| 2 |
Not Used |
� |
| 28 |
Not Used |
� |
| 3 |
Not Used |
� |
| 29 |
Not Used |
� |
| 4 |
Not Used |
� |
| 30 |
Not Used |
� |
| 5 |
Not Used |
� |
| 31 |
Not Used |
� |
| 6 |
Not Used |
� |
| 32 |
Not Used |
� |
| 7 |
Not Used |
� |
| 33 |
RFA2 + |
Rectifier Failure (positive) |
| 8 |
RFA2 - |
Rectifier Failure (negative) |
| 34 |
ACF2 + |
AC Failure (positive) |
| 9 |
ACF2 - |
AC Failure (negative) |
| 35 |
BIF2 + |
Battery Interface Failure (positive) |
| 10 |
BIF2 - |
Battery Interface Failure (negative) |
| 36 |
BOD2 + |
Battery On Discharge (positive) |
| 11 |
BOD2 - |
Battery On Discharge (negative) |
| 37 |
Not Used |
� |
| 12 |
RXD |
Receive Data |
| 38 |
TXD |
Transmit Data |
| 13 |
DTR |
Data Terminal Ready |
| 39 |
RS-232 GRD |
RS232 Ground |
| 14 |
DSR |
Data Set Ready |
| 40 |
RTS |
Request To Send |
| 15 |
Not Used |
� |
| 41 |
Not Used |
� |
| 16 |
Not Used |
� |
| 42 |
Not Used |
� |
| 17 |
Not Used |
� |
| 43 |
Not Used |
� |
| 18 |
Not Used |
� |
| 44 |
Not Used |
� |
| 19 |
Not Used |
� |
| 45 |
Not Used |
� |
| 20 |
Not Used |
� |
| 46 |
Not Used |
� |
| 21 |
Not Used |
� |
| 47 |
Not Used |
� |
| 22 |
Not Used |
� |
| 48 |
Not Used |
� |
| 23 |
Not Used |
� |
| 49 |
Not Used |
� |
| 24 |
Not Used |
� |
| 50 |
Not Used |
� |
| 25 |
Not Used |
� |
|
|