DEFINITY Made Easy Home Page Table of contents Previous page Next page Index Links Frequently asked questions
Go to Upgrades for si Go to Installation for MCC Go to Installation for SCC



Connect Single-Carrier Cabinet Ground

Return to Task List

  1. Measure and cut a length of 4 AWG (#5) (21 mm 2) wire long enough to reach between the GROUND DISCHARGE bar on the DC Power Cabinet and the single-point ground block on the Control Cabinet (bottom cabinet in Single-Carrier Cabinet Ground).

  2. At the DC Power Cabinet, connect the 4 AWG (#5) (21 mm 2) wire to the GROUND DISCHARGE bar.

  3. Route the wire to Control Cabinet and connect to the single-point ground block.

  4. Repeat for each Control Cabinet in the system room (duplicated Control Cabinet and Expansion Control Cabinet).

Single-Carrier Cabinet Ground

Figure Notes:
      1. 4 AWG (#5) (21 mm 2) Wire

      2. Control Cabinet (Cabinet A)

      3. Single-Point Ground Block

      4. To Additional Control Cabinets in Same Room

      5. DC Power Cabinet

      6. Ground Discharge Bar