Install and Connect Single-Carrier Cabinets
Connect DC Power Distribution Unit Ground
- Measure and cut a length of 4 AWG (#5) (21 mm 2) wire long enough to reach between the GROUND DISCHARGE bar in the DC Power Cabinet and the GRD connector on the DC Distribution Unit. See DC Power Distribution Unit Ground.
- At the DC Power Cabinet, connect a the 4 AWG (#5) (21 mm 2) wire to the GROUND DISCHARGE bar.
- Route the opposite end of the wire to the DC Power Distribution Unit and connect the wire to the GRD connector.
- Repeat Steps 2 and 3 for each remaining DC Power Distribution Unit.
DC Power Distribution Unit Ground
Figure Notes:
| Copyright� 2001 Avaya Inc. |